Digital PDFs
Documents
Guest
Register
Log In
EK-KMV1A-IG-001
May 1987
40 pages
Original
8.7MB
view
download
OCR Version
4.2MB
view
download
Document:
KMV1A-S Communications Controller for the BA200-Series Enclosure
Order Number:
EK-KMV1A-IG
Revision:
001
Pages:
40
Original Filename:
OCR Text
KMV1A-S COMMUNICATIONS CONTROLLERFORTHE BA200-SERIES ENCLOSURE Installation Guide Order No. EK-KMV1A-1G-001 digital equipment corporation maynard, massachusetts 1987 The information in this document is subject to change without notice and should not be construed as a commitment by Digital Equipment Corporation. Digital Equipment Corporation assumes no responsibility for any errors that may appear in this document. The software described in this document is furnished under a license and may be used or copied only in accordance with the terms of such license. @ No responsibility is assumed for the use or reliability of software on equipment that is not supplied by Digital Equipment Corporation or its affiliated companies. Copyright ©1987 by Digital Equipment Corporation All Rights Reserved. Printed in U.S.A. The postpaid READER'S COMMENTS form on the last page of this document requests the user’s critical evaluation to assist in preparing future documentation. The following are trademarks of Digital Equipment Corporation: DEC DEC/CMS DEC/MMS DIBOL EduSystem IAS UNIBUS VAX VAXduster DECsystem-10 DECSYSTEM-20 PDP PDT VT DECnet DECUS DECwriter MASSBUS RSTS RSX VMS . Bfl@nan 1 1 This document was prepared using VAX DOCUMENT, Version 1.0 TM Contents Preface v Chapter 1 INTRODUCTION 1.1 BA200-Series Enclosure. . . . .. ... 1.2 KMVIAHardware .. ...........c0iiiitinnnnnennn. R Chapter 2 ... ittt cees I L I P 141 B INSTALLATION 21 General . ... e e e e e e e e e e e 2-1 22 Unpacking the Option Kit . . . ... .outeeettin s iiineee s, - 2-1 2.3 Inspecting the EOSand FCCClips .................e PP . 2-2 2.4 Software Backup and Operating System Shutdown . . . ............. e s h ks . 22 2.5 Testingthe Existing System . ... ...............ciiiiiirnnn.. e 2-3 2.6 2.7 Checking the System Configuration . . . .. .........cotiununennene.n... 2-4 Guidelines for Module Placement . . . ... .................... .. 2-8 2.71 2.8 Bus Continuity ............T T .o e e e b .. 2-8 272 PowerSupplies ................ P .. 273 ModuleOrder. 2-8 2.74 Determining CSR Addresses and Interrupt Vectors 2.7.5 Determining Addresses and Vectors using CONFIG . ................ 2-10 2.7.6 Determining CSR AddressesusingaTable . . .. ................... 2-11 2.7.7 Examples of setting the CSR Address and Interrupt Vector 27.8 Interfaces . ... ... ... 279 TestSwitches . ... ...... .. .. ... . . .. ....... .ttt i i e e 2-9 ... . ................ i Relocating existingModules . . . ........ ... .. ... ... . . e 2-9 . ...........2-12 e e e e e 2-13 e 2-13 i e, 2-14 2.8.1 Removing Modules with Blank Covers . . . .. ..........c.0ovueunn. 2-15 2.8.2 Removing ModuleswithHandles . ............................ 2-15 29 Installing the KMVIA . . ... ... ... 2.10 Verifying the Ground Connections . ittt e 2-16 . .. ... ... .. ... ... il it nnneenns 2-19 2.11 Connecting to External Devices Chapter 3 . ... .... ... .. ... ... . . . . .. 2-19 TESTING THE CONFIGURATION 3.1 MicroVAX Systems . . . .. ... ... 3-1 32 MicroPDP-11Systems . . . ... .. .....oouinn.... P 3-5 Figures 1-1 BA213 Enclosure Chassis, BA200-Series. . . . .. ... ................. 12 2-1 KMV1A-S Series Option Kit Contents for BA200 Series Enclosure 2-3 2-2 Inspectingthe EOSand FCCClips . . ........ ... ... . ... .. ..., 2-5 2-3 2-4 BA200-Series Enclosure Configuration Worksheet ........ . .. ... ............. 2-6 Bus Grant Continuity Path . . . .. .............................. 2-8 2-5 Switch Pack Locations . . ... ..... ... .. . ... . . . . . ..., 2-14 2-6 Releasing the Captive Screws . . . . .. ..................e 2-7 Unlocking the Release Levers 2216 . ... ......... ... ... .. ... .. ..., 2-17 2-8 ImsertingtheModule . ... ... .. .. ... . ... . .. . . . 2-18 2-9 Attaching the Gap Filler Assembly . . ... ...... ... .. . . 2-10 Connecting to External Devices . .. ... ... ....... ... ... ......... 2-21 ... ... ..... 2-20 Tables 1 2-1 2-2 2-3 Associated Documents . . .. ... ... ... L e . PowerandBuslLoadData ................................... vi 27 Entries to use with the SYSGEN Utility . .........................2-11 Floating CSR Addresses . . ... ... ..... ... ..., 2-11 2-4 Settingthe CSR Address -E29 . . . . . .. .. ... ... .. .. . 2-5 Setting the Vector Address -E13 . ... ... ...... ... ... 2-12 .. ... ... ..... 2-12 2-6 Setting the Interfaces - Switch Pack E85 . .. ... ............ e 2-13 2-7 Setting the Self-test Switches - Switch Packs 13and29 ... ............. 2-13 v Preface This installation guide chvides the information and procedures necessary to install and test the KMV1A-SF, the KMV1A-SG or the KMV1A-SH Programmable Communications Controller option kit in the BA200-series microsystem enclosure. It is only intended for use by DEC field service personnel or qualified self-maintenance customers. It is the customer’s responsibility to do a software backup prior to installing the KMV1A-S. This step is important to safeguard against data being lost during the installation process. If you are not qualified to install a KMV1A-S series option kit, call Digital Field Service to schedule an installation. If you are to perform the installation of a KMV1A-S series option kit, make sure you are wearing an anti-static wrist strap connected to a grounded anti-static workstation before you handle it. It is susceptible to damage by static discharge. Also, ensure the bus grant continuity path is intact after the installation; no vacant backplane slots should exist between modules. If you have any difficulty in performing the installation, call Digital Field Service for assistance. Be sure to take anti-static precautions when unpacking and installing the module. Use the groundstrap and anti-static mat contained in the Anti-Static Kit, P/N 29-26246-00. The AntiStatic Kit is not included in the installation kit. It is part of the field service kit. Diagnostics The diagnostics for the KMV1A are released through the Software Distribution Center (SDC). The following options can be ordered separately by self-maintenance customers, according to the type of processor they have. 1. For the MicroPDP-11 family: e ZJ]-360-RZ diagnostic documentation kit e Z]-360-FR diagnostic fiche kit e Z]-360 diagnostic kit 2. For the MicroVAX family, the diagnostics are included in the MicroVAX MDM set of test programs. Table 1: Associated Documents Title Order number KMV1A Programmable Communication Controller User’s Guide EK-KMV1A -UG MicroVAX System Maintenance EK-O01AA-MG Guide' MDM User’s Guide AA-FM7A-DN MicroPDP-11 Systems Technical Manual EK-MIC-11-TM-002 1This document is included in the MicroVAX System Kit. Customers who have trouble with their equipment during the installation should call their local DEC field service engineers. vi Chapter 1 INTRODUCTION 1.1 BA200-Series Efnclosure" The BA200-series enclosure has a 6-slot or 12-slot, Qbbus backplane and one or two modular power supplies. Figure 1-1 shows the 12-slot BA213 enclosure chassis. The backplane uses the Q22-bus in the AB rows‘of each slot. The CD interconnect is used in all 12 slots. MicroVAX systems use the CD rows of slats 1 through 3 for their high-speed memory interconnects. BA200-series enclosures with mass stsrage a held up to four standard 13.3 em (5.25 inch) devices (three disk drives and one tape drive). Fixed disk drives face the rear of the enclosure, providing easy access to their drive signal and power cables. The major difference between the BAZOO-»ser:es and other microsystem enclosuresis in the way you connect external devices to the system. Option modules in the 'BA200-series enclosure connect directly to external I/O connectors. Other enclosures require an insert panel and internal cabling between the option module and the device. A There are two main differences between themcéules usedin the BAZOO-senes enclosure and those usedin the other microsystem enclosures: * Option modules for external devices have bulkhead handles. These handles replace the insert panels and internal cabling foundin the BA23 and the BA123 enclosures. * Standard Q22-bus modules (such as the RQDX3 and TQK50) have blank bulkhead covers. The module handles and blank covers form an electrical seal that complies wzth FCC regulations for (1) keeping frequencies generated by the system in the enclosure, and (2) keeping radio frequencies out of the enclosure. See the MicroVAX System Maintenance Guide for further mfermatmn on the BAZO@-senes enclosure. Figure 1-1: BA213 Enclosure Chassis, BA200-Series 1.2 KMV1A Hardware The KMV1A hardware consists of a quad-height board, an indicator panel, and a line connector cable. It is designed to be used in a communication link by Q-bus based systems. The KMV1A is microprocessor based and able to perform functions for bit-oriented synchronous protocols (like HDLC), byte-oriented synchronous protocols (like BSC), or asynchronous protocols. The application firmware defines the computer instructions that are needed to execute the protocolrelated activities. 1-2 INTRODUCTION Features of the KMV1A include: e Direct Memory Access (DMA) across the Q-bus for medium-speed transmission and reception. e A DCT11 microprocessor with the PDP-11 base level instruction set. * A7201 PUSART (Programmable Universal Synchronous/Asynchronous Receiver/Transmitter) line controller chip. * An EPROM of 8K bytes, with root firmware and power-up self-test diagnostics. e RAM space of 32K bytes, for implementation of data-link protocols. * Synchronous (bit-oriented or byte-oriented) as well as asynchronous capabilities for the application firmware. * Extensive support of modem signals. * An on-board null modem clock. The KMV1A-SF option kit has the RS232-C electrical interface. The KMV1A-SG option kit has the RS422-A electrical interface. The KMV1A-SH option kit has the RS423-A electrical interface. All the aforementioned option kits are designed for installation in the BA200-series enclosure. See the KMV1A User’s Guide for further information. INTRODUCTION 1-3 Chapter 2 INSTALLATION 2.1 General This chapter prevxdes step-by-step procedures for ungackmg, inspecting, and installing the KMV1A-S series option kits in the BA200-series enclosure. It also discusses system and module configurations. 2.2 Unpacking the Option Kit 1. Look for external damage on the shipping container such as dents, holes, or crushed corners. 2. Do not dispose of the &cking material until you have installed the module and have successfully completed the testing. 3. Put on your anti-static wrist strap. 4. Attach the wrist strap and anti-static mat to the BA200-series enclosure metal chassis. Use the anti-static mat when locating the module. 5. Use the following checklist to identify the contents of your KMV1A-S series option kit (Figure 2-1): You should have one of the following: ¢ One M7500-PA module for the KMV1A-SF option kit * One M7500-PB module for the KMV1A-SG option kit * One M7500-PC module for the KMV1A-SH option kit You should have all of the following: * One filler kit consisting of two gap filler assemblies (70-24505-01). e One Installation Guide (EK-KMV1A-IG-001). e One KMV1A User’'s Guide (EK-KMV1A-UG). See Caution * One H3066 loopback connector for the KMV1A-SF * One H3067 loopback connector for the KMV1A-SG or KMV1A-SH | Caution | Not all the information contained in this guide is relevant for the KMV1A-S. Remove the KMV1A module from the anti-static bag. Inspect the module for shipping damage. Report any damage to the shipper and notify the Digital representative. 2.3 Inspecting the EOS and FCC Clips Note To comply with FCC regulations, the bulkhead handles, blank covers, and gap fillers are equipped with transient protection EOS and FCC clips; these clips are grounded through the module handle. 1. Ensure that there is no residue or corrosion on the FCC and EOS clips on the KMV1A handle (Figure 2-2). Also ensure that thereis no residue or corrosion on the FCC clips on the two gap fillers (Figure 2-2). If so, remove it with alcohol. 2. Ensure that the FCC and EOS clips are in an arched shape. When depressed slightly, they should return to their original shape. 3. If any clipis missing or broken, replace it with FCC clip P/N 12-26340-01. 2.4 Software Backup and Operating System Shutdown It is the customer’s responsibility to perform a software backup and then to shut down the operating system software. Ensure that the customer has taken these steps before starting the installation procedures. 2-2 INSTALLATION Figure 2-1: KMV1A-S Series Option Kit Contents for BA200 Series Enclosure !!fll H Eflififlfl?907 LORINOL LR dazs. SE!?!S !ttfliifi ; WETRLL 4100 Gup m7500.P° . ¥ _AMIVA [ . [ TR0 Wheie » . A B.C Versiens 00007 KBYIA Programmable Contralier User Soide 1 U U““"—"‘“fiflfl’fi seavws ) (\ = 2.5 Testing the Existing System 1. Ensure the existing system is running properly. Always remove the diskette/tape before turning the power off. Never work inside a system enclosure without first shutting off the system power. 2. After the successful completion of the test, remove the floppy or tape and turn the I/O power switch off. Unplug the ac power cord from the wall outlet. 2.6 Checking the System Configuration You must complete the BA200-Series Enclosure Worksheet (Figure 2-3) to make sure you do not exceed the system’s limits for power and bus loads. You need to gain access to the modules installed in the system backplane before you configure the system. Refer to the system’s documentation for procedures to help you remove any existing covers. ~ To check the system configuration, perform the following steps: 1. On the configuration worksheet, list all the modules already installed in the system; each module has an identifying label on the cover or handle. List the modules you plan to install in the systein, Fill in the information for each device in accordance with Table 2-1. Add up the columns. Make sure the totals are within the limits for the enclosure, given at the bottom of the Configuration Worksheet. 2-4 INSTALLATION Figure 2-2: Inspecting the EOS and FCC Clips FCC CLIP GAP FILLER ASSEMBLY FCC CLIPS EOS CLIPS BA200-Series Enclosure Configuration Worksheet "MASS STORA 00 55 TAPE 1 > DISK 1 TOTAL RIGHT HALP | P.S COLUMNS | " 330 MUST NOT EXCEED LEFT-HALF (ABcp) | MODULE POWER SUPPLY | [ CURRENT | CURRENT 5 230.0 1.0 12 ~ POWER LWATTS) 7 10 1" 12 MASS STORAGE >>> TAPE 2 >>> DISK 3 TOTAL LEFT HALF P.S COLUMNS MUST NOT EXCEED 33.0 10 TOTAL 2300 BUS LOADS == MUST NOT EXCEED >>> 2-6 INSTALLATION 2 POWER (WATTS ). CURRENT 12V 4 CURRENT 5Y = L RIGHT.HALFPOWER SUPPLY "~ o T =] IIINOOECEaRNEng: g I g [l fs[e [ TTITTT T 0 o Figure 2-3: | Table 2-1: Power and Bus Load Data DC Bus Option +5V +12V Watts AC Bus Load Load CXA16-M 1.6 0.29 115 3.0 1.0 CXB16-M 2.0 0.0 10.0 3.0 1.0 CXY08-M 1.8 0.43 14.2 3.0 1.0 DEQNA-SA 3.5 0.50 23.5 3.0 0.5 DPV11-SA 12 0.30 9.6 2.2 1.0 DRQ3B-SA 4.5 0.0 225 1.0 1.0 DRVIW-SA 1.8 0.0 9.0 2.0 1.0 DZQ11-SA 1.0 0.36 9.3 2.0 0.5 IBQO1-SA 5.0 0.30 28.6 14 1.0 IEQ11-SA 3.5 0.0 17.5 4.6 1.0 KA620-AA 6.2 0.14 32.7 2.0 1.0 KA630-AA 6.2 0.14 32.7 2.7 1.0 KDJ11-BF 5.5 0.20 29.9 2.6 1.0 KDJ11-SA/SB 3.47 0.19 19.6 3.0 1.0 KMV1A-SF/SG/SH 2.6 0.20 15.4 3.0 1.0 MRV11-D 1.6' 0.0 8.01 3.0 0.5 MS630-BB 1.8 0.0 9.0 0.0 0.0 MS6300-CA 3.1 0.0 15.5 0.0 0.0 MSV11-JD 3.74 0.0 18.7 2.7 0.5 MSV11-JE 4.1 0.0 20.5 2.7 0.5 MSV11-QA 2.4 0.0 12.0 2.0 1.0 M9060-YA 5.3 0.0 1265 0.0 0.0 RD53-EA 0.9 25 . 34.5 0.0 0.0 RD54-EA 1.3 1.34 22.6 0.0 0.0 RQDX3-M 2.48 0.06 13.1 1.9 0.5 TK50E-EA o135 2.4 35.6 0.0 0.0 TQK50 2.9 0.0 14.5 2.8 0.5 ! Value is for the unoccupied module only. INSTALLATION 2-7 2.7 Guidelines for Module Placement 2.7.1 Bus Continuity Bus grant signals pass through each installed module as shown in Figure 2.4. Use Bus Grant Continuity Cards (M9047) in vacant backplane slots to ensure bus continuity. Figure 2-4: Bus Grant Continuity Path éa §.. & e D 2.7.2 Power Supplies The BA200-series enclosure contains one or two separate 230-Watt power supplies. For enclosures with two power supplies, the first (right-side) power supply powers slots 1 through 6 and the second (left-side) one slots 7 through 12. Each power supply in the enclosure must have a minimum 5-Amp load on the 5-volt output to maintain regulation. If the minimum load requirement is not met, you must install a load module (M9060-YA) in an open backplane slot which is powered by that power supply. Otherwise, the power supply will enter an error mode and shut down the system. Refer to section 2.8 (Relocating Existing Modules) for procedures to install or remove modules. 2-8 INSTALLATION 2.7.3 Module Order Use the following recommended module order (from right to left in the BA200-series enclosure) to help you correctly install the KMV1A module. e CPU Board ¢ Memory board e MRVI11 e DPVIl e DRVI11.] e LPV1l e DLV]1 e DZQ11 e KMVI1A e DEQNA o CXAl6 e CXB16 e (CXY16 ¢ IEQ11 - No restrictions on position e IBQO1 - No restrictions on position ¢ TQKS50 e RQDX3 « DRQ3B e DRVIW - Should be the last device on the Q-Bus. 2.7.4 Determining CSR Addresses and Interrupt Vectors CSR addresses and interrupt vectors are fixed or floating. Fixed means there is a fixed location in memory reserved for the address or vector of a particular module. These modules are shipped with the correct address and vector settings for use as the first of their type. If they are not the first, then the settings of subsequent ones must be considered as floating; some modules only have floating addresses and vectors. A floating address or vector is assigned a location within an octal range. The exact location depends on what other modules are in the system. The ranges are as follows: e Floating CSR address: 17760010 - 17763776 * Floating interrupt vector: 300 - 777 If you have a MicroVAX system, use CONFIG, a program of the SYSGEN utility, to determine the CSR address and interrupt vector; see 2.7.5. If you don’t have this utility, see 2.7.6 to determine the address and vector values; substitute the numbers for nnn in 17760(nnn). Once you know the values, see 2.7.7 to set them. The address and vector settings are configured by switch packs E29 and E13 respectively; the locations of the packs are shownin Figure 2-5. Note To set switches of modules other than the KMV1A, refer to the user guides for the modules or the System Technical Manual. 2.7.5 Determining Addresses and Vectors using CONFIG Run this procedure to find the addresses of your new configuration. See Table 2-2, Entries to use with the SYSGEN Utility. STEP ACTION RESPONSE 1 Key in: MCR SYSGEN SYSGEN > 2 Key in: CONFIGURE DEVICE > 3 Key in: KMV11 DEVICE > 4 Hold down CTRL and press Z when you have keyed in all device identities CSR: address Vector: value Support: 5 Key in: EXIT System returns to the Mi- croVMS command prompt Note If there is more than one of the same device in the system, follow its identity by a comma and the number of devices. An asterisk next to a displayed address indicates that you can use the address, but if you change the configuration you must run SYSGEN again to find out if the address has also L. If Support reads ‘No’, a software driver for the module concerned is not included in the VMS based system. 2-10 INSTALLATION Table 2-2: Entries to use with the SYSGEN Utility Device | Entry made at the Device Prompt DPV11 DPV11 LPV11 LP11 DEQNA UNA KLESI, TQKS50 or TQK70 TU81 RQDX3 or KDAS50 UDA CX Series DHV11 2.7.6 Determining CSR Addresses using a Table The following table gives module addresses for four typical configurations; only use it if you don’t have SYSGEN. See Note when determining vectors. Table 2-3: Floating CSR Addresses Example configurations 1 to 4 Device 1 2 3 4 270* 270> 270+ 270* 2nd MSCP 404+ 404+ 404+ 404+ KMV1A 420 420 420 420 440 440 500 500 DPV11 | KMV1A CX series 460 CX series 520 * The presence or absence of this device will not affect other addresses in the configuration. MSCPis the abbreviation for Mass Storage Control Protocol. 1tis the collective name used for KLESI, TQK50 AND TQK70 devices. Note When setting vectors, begin at 300 for the first module and increment the address by 10 for each subsequent device in the following order: DPV1l, 2nd MSCP, then the KMV1A followed by the CX series. INSTALLATION 2-11 2.7.7 Examples of setting the CSR Address and Interrupt Vector The following shows the factory setting and other common settings: Table 2-4: Setting the CSR Address - E29 Address Switch settings 9 8 7 6 5 4 3 2 17760420+ 0 0 0 0 1 0 0 0 17760460 0 0 0 0 1 0 0 1 17760520 0 0 0 0 1 0 1 0 1=0N, 0=0OFF/OPEN * This is the factory setting. Interrupt vectors are set in the same way: Table 2-5: Setting the Vector Address - E13 Address Switch settings 7 6 5 4 3 2 1 300+ 0 0 1 1 0 0 0 310 0 0 1 1 0 0 1 320 0 0 1 1 0 1 0 1=0N, 0=0OFF/OPEN * This is the factory setting. 2-12 INSTALLATION 2.7.8 Interfaces You should check switch pack E85 as follows. Its location is shown in Figure 2-5. Setting the Interfaces - Switch Pack E85 Table 2-6: Switch Settings Interface type 10 9 8 7 6 5 4 3 2 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 RS-232C RS-422A 1 RS-423A 1 0 0 0 0 1 1 1 1 1 1 1 1 1 1=0ON, 0=0FF/OPEN Note All the above are factory settings. " Corresponding Modules RS-232C — M7500-PA RS-422A — M7500-PB RS-423A — M7500-PC 2.7.9 Test Switches | You should check the test switches as follows. Their locations are shown in Figure 2.5. Setting the Self-test Switches - Switch Packs 13 and 29 Table 2-7: Switch Pack | 13 29 - Switch Switch Setting 8 1 10 0 1=0ON, 0= OFF/OPEN " Note All the above are factory settings. The settings ensure that a self test is activated at power up. : i il BBE 1 | B Ty 7\3 il BE6BBRAAAR Figure 2-5: Switch Pack Locations 2.8 Relocating existing Modules Caution Only qualified service personnel should remove or install modules. If the slot into which you plan to install the KMV1A is empty, go to section 2.9. If it already contains a module use the following procedures to relocate the KMV1A in the backplane. 2-14 INSTALLATION ol 2.8. Removing Modules with Blank Covers Caution Make sure you are wearing a grounded anti-static wrist strap when you remove or install modules. 1. Release the two%-turn captive screws that hold the blank cover to the card cage (Figure 2-6). Pull the blank cover away from the card cage. Note the orientation of any internal cables connected to the module; some connectors are not keyed. Carefully label and disconnect them. L 4. Unlock the module release levers by simultaneously pulling up on the top lever and pulling down on the bottom lever. For modules with a plastic handle, pull out on the plastic | handle. Carefully pull the module out of the card cage. Confirm the module’s CSR address and interrupt vector; see section 2.7.4 for help in determining the correct setting. Change switch settings if necessary. If no change is necessary, be careful not to disturb any switch packs on the module. 7. Reverse this procedure to install the module in its new location. Do not fasten the %-turn screws until you have installed the KMV1A module. 2.8.2 Removing Modules with Handles Caution Make sure you are wearing a grounded anti-—stati:: wrist strap when you remove or install modules. 1. Note the orientation of external cables connected to the module. Carefully label and disconnect them. 2. Releasezthe two %-turn captive screws that hold the handle of the module to the card cage (Figure 2-6). 3. Simultaneously unlock the release levers by pulling up on the top lever and pulling down on the bottom one (Figure 2-7). @ S Pull on the handle of the module to remove it from the slot. 5. Confirm the module’s CSR address and interrupt vector; see section 2.7.4 for help in determining the correct setting. Change switch settings if necessary. If no change is necessary, be careful not to disturb any switch packs on the module. 6. Reverse this procedure to install the module in its new location. Do not fasten the %-turn screws until you have installed the KMV1A module. Figure 2-6: Releasing the Captive Screws 10 RELEASE - PUSH IN: TURN COUNTER CLOCKWISE 114 TURW TO FASTEN PUSH IN, TURN CLOCKWISE 1/4. TURN 2.9 Installing the KMV1A Caution Be careful not to snag the module’s components on the card guides or adjacent modules. 1. Insert the KMV1A module into the appropriate card slot using the recommended module order listed in section 2.7.3. 2-16 INSTALLATION Unlocking the Release Levers L ] 1 v w Figure 2-7: 2. Holding both the top and bottom release levers, lock the module in place by simultaneously pushing the top lever down and pulling the bottom one up (Figure 2.8). 3. Do not fasten the %-turn captive screws. Verify the ground connections first (section 2.10). N 2-17 Figure 2-8: inserting the Module o 4H &m »O ,Z 2.10 Verifying the Ground Connections Caution When you install a module with a blank cover or flush handle next to a recessedhandle module, you must install a gap-filler assembly between the modules to meet FCC regulations. Without it, circuitry on the recessed-handle module will be exposed. Two gap filler assemblies (P/N 70-24071-01) are provided with the option kit. Each assembly includes one gap filler and two screws. Verify that the ground connections (Figure 2-9) are correctly in place as follows: 1. Check to see if any recessed-handle module in the backplane has a module with a blank cover or a flush handle in the slot immediately before or after it. If so, verify that a gap filler assembly is installed on the side of the blank cover or flush handle that is next to the recessed-handle module | | | Note There should not be any open spaces between the modules in the backplane. Fasten the %-turn captive screws on all handles and covers in the backplane. If an open space exists, install the gap filler assembly as follows: a. Using two screws and oz;:niap filler (P/N 70-24505-01), attach the g‘ap filler to the top and bottom of the side blank cover or flush handle that fits next to the recessed-handle module. Make sure the gap-filler tabs fit into the tab indentations on the blank cover flush handle (Figure 2-9). b. Place the blank cover with the gap filler over the card cage slot, or insert the flush handle module with the gap filler into the card slot. ¢. Ensure that there is correct ground (no open spaces) between the two modules. d. Fasten the %-turn captive screws on all handles and covers in the backplane. 2.11 Connecting to External Devices See Figure 2-10 for connecting to external devices and observe the following: e Use a BCC 04 cable for the KMV1A-SF. e Use a BC 18Y cable for the KMV1A-SG/SH. These cables are not supplied with the KMV1A. They can, however, be ordered from DECdirect. ON 2-19 Attaching the Gap Filler Assembly -3 o b4 Figure 2-9: ~ * P . & SLAMK CoveR THE GAP FILLER IS MOWNTED ONTO THE BLANK COVER 10 © 2-20 CLOSE THE OPEN SPACE BETWEEN THE RECESSED MOBWLE ANO THE BLANK COvER INSTALLATION Figure 2-10: Connecting to External Devices INSTALLATION 2-21 Chapter 3 TESTING THE CONFIGURATION 3.1 MicroVAX Systems Note Loopback connectors are not required for testing communication devices at tlus level. All data input must be terminated by the RETURN key. The procedure uses a tape, this being the device most commonly used. If you have problems with the procedures, keyin HELP at any time for advice STEP ACTION RESPONSE 1 Switch on I/O switch on front panel Lamp in switch lights 2 LED on the KMV1A Check the green light after about 1t should 10 seconds. Thefollowing ld Read be displayed. shou it and take the ac- in bold charactions given KA630-A.V1.3 Performing normal system tests. Tests completed. Load the uVAXII Diagnostic Customer TK50 Tape. The following appears: >>> Key in: b mu0 The following appears. Carry out actions as requested. 2..1..0.. %VAXELN system initializing TESTING THE CONFIGURATION 3-1 VAXELN V2.4-00 MicroVAX Diagnostic Monitor - Version 2.02 CONFIDENTIAL DIAGNOSTIC SOFTWARE PROPERTY OF DIGITAL EQUIPMENT CORPORATION Use Authorized Only Pursuant to a Valid Right-to-use License Copyright (c) 1986,1987 Digital Equipment Corporation The current date and time is: 2-OCT-1987 08:42:07.07 Press the RETURN key to continue, or enter the new date and time; then press the RETURN key. [DD-MMM-YYYY HH:MM]: The current date and time is: 2-OCT-1987 08:42:10.55 The system is preparing for testing. This may take several minutes. Please wait ... The system is rea:dy for testing. Press the RETURN key to continue. 1 - Test the system 2 - Display System Configuration and Devices 3 - Display the System Utilities Menu 4 - Display the Service Menu 5 - Exit MicroVAX Diagnostic Monitor Type the number; then press the RETURN key. 2 MAIN MENU SYSTEM CONFIGURATION AND DEVICES CPUA ... MicroVAX/RTVAX CPU KA630-AA 1MB, FPU MC =00 HW =00 MEMA ... MicroVAX/rtVAX memory system 5 megabytes. 10240 Pages. 3-2 TESTING THE CONFIGURATION KA630 ... CPU module, IMB on-board memory MS630-BB ... Quad height memory module, 4MB RQDXA ... Winchester/diskette controller. Revisions =2 and 1 RD53 ... Nonremovable KMV1AA ... Programmmable communications interface for Q-bus PROM Revision - 2 TK50A ... TK50 CONTROLLER REV FW =4 Press the RETURN key to return to the previous menu. 1 - Test the system 2 - Display System Configuration and Devices 3 - Display the System Utilities Menu 4 - Display the Service Menu 5 - Exit MicroVAX Diagnostic Monitor Type the number; then press the RETURN key. 1 MAIN MENU SYSTEM TEST This is a test of the MicroVAX computer and its devices. No additional preparation for this testing is required; the MicroVAX is ready to be tested. Testing occurs in two parts: the functional tests quickly test each device sequentially; the exerciser test (lasting about 4 minutes) tests how many devices work together. To halt the test at any time and return to the Main Menu, type CTRL-C by holding down the CTRL key and pressing the C key. BEGIN DEVICE TESTS This is a test of all system devices identified by the system. If any of your system devices are not listed below, consult your system documentation for the action to take. Device CPU ......... MEMA ........ RQDXA ....... KMVIA ....... TK50A ....... Result passed passed passed passed passed BEGIN EXERCISER TEST Results are reported at the end of the testing. TESTING THE CONFIGURATION 3-3 SYSTEM TEST PASSED All devices passed functional tests and the system passed the exerciser test. At this point you may exit from the MicroVAX Diagnostic Monitor or perform more specialised testing. If you would like additional information, consult the system documenta- tion. Press the RETURN key to return to the previous menu. MAIN MENU 1 - Test the system 2 - Display System Configuration and Devices 3 - Display the System Utilities Menu 4 - Display the Service Menu 5 - Exit MicroVAX Diagnostic Monitor Type the number; then press the RETURN key. 5 MicroVAX Diagnostic Monitor - Version 2.02 Exiting MicroVAX Diagnostic Monitor. Exit complete. You may now load your system software. Note If the KMV1A is not specified in the system configuration display or if it fails the device test, check its switch pack settings. If they are alright call DEC field service. 3-4 TESTING THE CONFIGURATION 3.2 MicroPDP-11 Systems Note A loopback connector is not required for testing the KMV1A at this level. All data input must be terminated by the RETURN key. STEP ACTION RESPONSE Insert the diagnostic kit. Switch on 1/O switch on front panel. Lamp in switch lights. ‘BOOTING FROM Mn’ displayed. Check the green LED on the KMV1A. It should light after about 10 seconds. Key in: R VKMA?? ‘DR >’ is displayed. Key in: START ‘'CHANGE HW (L) ?’ is displayed. Keyin: Y "UNITS (D)’ is displayed. Key in: Number of KMV1A's installed Addresses requested. Key in: Last six figures of KMV1A address. Replace the Vector requested. 9 Key in: KMV1A vector Priority level requested. 10 Press RETURN 'RUNNING ON UNIT' is displayed. Test runs continuously until you press CTRL C. Do this when 'EOP (End of Pass) 5’ is displayed. Fit the loopback connector to the KMV1A. Repeat the test, this time keying in R VKMB?? in STEP 4 instead of R VKMA?? Note If the KMV1A fails the device test, check its switch pack settings. If they are alright call DEC field service. TESTING THE CONFIGURATION 3-5
Home
Privacy and Data
Site structure and layout ©2025 Majenko Technologies